480H

The Model 480H is a state-of-the-art high concentration ozone monitor. The 480H provides accurate and stable readings over long time periods and was designed with the user in mind. The modular design allows for easier field serviceability. The Model 480H is housed in a splash-proof NEMA 4X wall mount enclosure.

Call For Price

The sensor module contained in the Model 480H uses detectors with a very narrow band of spectral sensitivity, eliminating the need for UV band pass filters which are subject to deterioration by UV or humidity. Two detectors are used: one for the ozone measurement, and the other to compensate for changes in UV source intensity. This unique design enables the sensor to operate for extended periods without calibration or maintenance.

The mercury-free UV LED source in the detection cell makes this process ozone monitor the first of its kind.​

Built-in diagnostics provide warning signals range. Test values can be viewed while the Model 480H is operating. These displays, warnings, and self-diagnostics, along with the modular design, allow maximum uptime. In addition, any function that can be set or monitored from the front panel can be remotely set or viewed.​

The graphical display and user-friendly interface allow for quick checks of measurements and easy adjustment of settings. Improved communication interfaces allow for greater productivity.​​

Features:

- UV Absorption Method

- Intuitive graphical user interface

- Mercury-free UV LED source

- Ranges 0-5 to 0-25% w/w

- Built-in diagnostics/error logs/warning alarms

- Modular internal design

- Minimal zero drift

- Programmable auto-zero function included

- Programmable concentration alarms

- Temperature and pressure compensation (standard)

- Ethernet standard​, WiFi (coming soon)

Specifications:

Measurement PrincipleUV Absorption (Beer Lambert Law) UV Absorption (Beer Lambert Law)
Ranges 0-5% w/w to 0-25% w/w
0-100 g/Nm3 to 0-400 g/Nm3
Measurement Units % w/w, g/Nm3
Accuracy ± 1% of full scale
Precision/Repeatability ± 0.5% of full scale​​
Display Resolution 0.01% w/w, 0.1 g/Nm3
Response Time < 30 seconds to 95%
Compensation Pressure, Temperature
(NTP = 273.15K, 760mmHg)
Gas Inlet Pressure Range 3.0 - 30.0 psig​
Gas Flow R​ate 0.2 - 2.0 LPM
Temperature Range 5 - 45°C
Dimensions (H x W x D) NEMA 4X - 17.35” x 15.96” x 6.80” (440.7 mm x 405.4 mm x 172.7 mm)​
​Weight NEMA 4X - 17.6 lbs (8kg)
Power 110-240V, 50/60Hz, 74W
Analog Output 0-5V or 4-20mA isolated output
Status Outputs Optically isolated Digital Outputs
Sensor OK, Invalid Reading, Check Lamp, Pneumatic Error​
24VDC, 30mA per output​
High Current Relay Outputs SPDT Form C Dry contact, 250VAC/5A
(System OK, HI Alarm, HI-HI Alarm)
Communication Interface RS-232, RS-485​
Ethernet​
WiFi (coming soon)
Degree of Protection (NEMA) IP65 (NEMA 4X)​
Approvals CE
Warranty 1 year

Downloads:

480H Manual

480M Specifications

Sample Conditioning – Ozone in High Humidity Environments

More Information
Manufacturer Oxidation Technologies
Call For Price No
4-20 mA Output Yes
Relays 1 Relay
Maximum Range 0-5% , 0-100 g/Nm3
Minimum Range 0-25% , 0-400 g/Nm3
Accuracy ​± 1% of full scale
Min, Max, Avg No
Voltage Output 0-5 V
Power Requirements 110-240V, 50/60Hz, 74W
Datalogging No
Rechargeable No
Warranty 1 Year
Audible Alarm Yes
Calibration Annually
Range 0-100 g/Nm3 to 0-400 g/Nm3
Unit Features

- Intuitive graphical user interface

- Mercury-free UV LED source

- Built-in diagnostics/error logs/warning alarms

- Modular internal design

- Minimal zero drift

- Programmable auto-zero function included

- Programmable concentration alarms

- Temperature and pressure compensation (standard)

- Ethernet standard​, WiFi (coming soon)

Sensor Range

0-100 g/Nm3 to 0-400 g/Nm3

Resolution 0.01 %
Integrated Relays Yes
Sensor Range

0-100 g/Nm3 to 0-400 g/Nm3

Write Your Own Review
You're reviewing:480H