B12 Ozone Detector

ATIs B12 Ozone Detector is a loop-powered instrument that offers a visual display, or transmits ozone levels via 4-20 mA signal.  No relays or controls functions are available.

As low as $625.00

The B12 Ozone Detector is a two-wire 4-20 mA transmitter that is loop-powered to signal linearly proportional to ozone gas concentration. They operate from a 24 VDC power supply and the transmitter will drive loads up to 675 ohms, which is sufficient for most monitoring applications. For applications that require battery operation they can operate at 12 VDC with a reduced output load. The electrochemical sensors are designed for use in ambient air or in ventilation ducts, and are not recommended for use in extremely dry air or in condensing gas streams. The sensor is located in one of the knockouts, and additional knockouts are provided on the sides of the transmitter to simplify installation.

The V12 is available with a vareity of gas sensors other than ozone.  See the drop down above for complete list of gas options.

The dimensions of the B12 Gas Transmitter

The typical set up and connections on the B12 Gas Transmitter

Transmitters are normally supplied with the sensor close coupled to the NEMA 4X polystyrene enclosure. An optional LCD display can be ordered and is installed on the face of the enclosure and is great for getting the gas concentration. (NOTE: the display must be ordered at the time the order is placed, this cannot be added later).  

B12 with the built in LCD display

The B12 can also be purchased in an explosion-proof transmitter enclosure that is made out of galvanized steel. Please specify that you want this enclosure by using the drop down under the Enclosure Options and selecting the Explosion-Proof Enclosure. (Picture below).

Explosion Proff Enclosure for the B12

For special applications, a separate sensor can be used that allows you to be up to 25 feet away from the transmitter. Sensor duct mounting adapters can be provided which allows the sensor to be inserted into a duct or pipe through a special adapter. This allows for easy removal of the sensor for service.

 

 Duct Mount Sensor Installation

Pictured above is the Flowcell assembly for the explosion-proff sensor (Part Number: 00-0298).

B12 Options (Guide to ordering)

Sensor Module:

Choose the gas detection required for your application.  Range shown is standard range; each sensor can be calibrated for a custom range for an additional $50.  See chart below to see minimum and maximum detection ranges for each sensor.  Contact us for details on this and to verify we can calibrate for your specific range.

Display, Enclosure & Transmitter:

     -NEMA 4X - this is the standard enclosure which is suitable for many environments.

     -Explosion-proof Enclosure - This version is made out of galvanized steel.  The LCD display is not possible with this model.

     -Explosion-proof Enclosure with Dual Condulet - Allows you to have a transmitter up to 25 feet away from the junction box.

     -With LCD display - provides local indication of gas concentration (built into front of the enclosure).

     -With Separated Sensor - sensor is separated from the transmitter and can be placed up to 25 feet away (cable included).

     -With LCD display and separated sensor - includes the LCD display and sensor is separated from the transmitter and can be placed up to 25 feet away (cable included).

     -With duct insertion sensor - Sensor duct mounting adapters allows the sensor to be inserted into a duct or pipe, and placed up to 25 feet away (cable included)

     -With LCD display and duct insertion sensor - includes the LCD display and sensor duct mounting adapters allows the sensor to be inserted into a duct or pipe.

Specifications

 Accuracy  Generally ±5% of value, but limited by available calibration gas accuracy
 Electronic Repeatability  ±1%
 Electronic Linearity  ±0.5%
 Zero Drift  Sensor dependent, but generally less than 1% of full scale per month, non-cumulative
 Span Drift  Application dependent, but generally less than 3% per month
 Output  Loop-powered 4-20 mA, 750 ohms maximum at 24 VDC
 Power  12-30 VDC
 Display  None. Optional LCD display available
 Enclosure  NEMA 4X Polystyrene Explosion-proof cast iron optional, Class 1, Div. 1, Groups B, C, & D.
 Controls  Zero and span potentiometers mounted on transmitter circuit board
 Operating Temperature  -30º to +55º C (except oxygen, which is -10º to +55º C)
 Sensor Pressure Limits  7-30 PSIA (0.5-2 Bar)
Calibration  Your sensor should be replaced annually

 

Sensor Range Specifications:

Please contact us with any questions on what sensor might be right for you, or if other sensors are available for your application.

Gas Min Range Max Range Standard Range
Acetylene 0-500 ppm 0-2000 ppm 0-1000 ppm
Acid Gases 0-10 ppm 0-200 ppm 0-10 ppm
Alcohol 0-500 ppm 0-2000 ppm 0-1000 ppm
Ammonia 0-100 ppm 0-2000 ppm 0-100 ppm
Arsine 0-1000 ppb 0-2000 ppm 0-1000 ppb
Bromine 0-1 ppm 0-200 ppm 0-2 ppm
Carbon Monoxide 0-100 ppm 0-1000 ppm 0-100 ppm
Chlorine 0-1 ppm 0-200 ppm 0-10 ppm
Chlorine Dioxide 0-1 ppm 0-200 ppm 0-2 ppm
Diborane 0-1000 ppb 0-2000 ppm 0-1000 ppb
Ethylene Oxide 0-20 ppm 0-200 ppm 0-20 ppm
Fluorine 0-1 ppm 0-200 ppm 0-2 ppm
Formaldehyde 0-20 ppm 0-200 ppm 0-20 ppm
Germane 0-1000 ppb 0-2000 ppm 0-1000 ppb
Hydrogen 0-1000 ppm 0-10% 0-4%
Hydrogen Chloride 0-10 ppm 0-200 ppm 0-20 ppm
Hydrogen Cyanide 0-20 ppm 0-10 ppm 0-200 ppm
Hydrogen Fluoride 0-10 ppm 0-200 ppm 0-20 ppm
Hydrogen Selenide 0-1000 ppb 0-2000 ppm 0-1000 ppb
Hydrogen Sulfide 0-10 ppm 0-500 ppm 0-50 ppm
Hydrogen Peroxide 0-10 ppm 0-2000 ppm 0-10 ppm
Iodine 0-1 ppm 0-200 ppm 0-2 ppm
Nitric Oxide 0-50 ppm 0-500 ppm 0-100 ppm
Nitrogen Dioxide 0-10 ppm 0-200 ppm 0-20 ppm
Oxygen 0-5% 0-30% 0-25%
Ozone 0-1 ppm 0-200 ppm 0-2 ppm
Phosgene 0-1 ppm 0-100 ppm 0-2 ppm
Phosphine 0-1000 ppb 0-2000 ppm 0-1000 ppb
Silane 0-10 ppm 0-2000 ppm 0-10 ppm
Sulfur Dioxide 0-10 ppm 0-200 ppm 0-20 ppm

 

 

Downloads:

     -B12 Product Spec Sheet

     -B12 Manual

     -B12 Dimensions Drawings

     -B12 Typical Specification

More Information
Manufacturer ATI
Call For Price No
Gas Acid Gases, Acteylene (C2H2), Alcohol, Ammonia (NH3), Arsine (AsH3), Bromine (Br2), Carbon Monoxide (CO), Chlorine (Cl2), Chlorine Dioxide (ClO2), Diborane (B2H6), Ethylene Oxide (ETO), Fluorine (F2), Formaldehyde (CH2O), Germane (GeH4), Hydrogen (H2), Hydrogen Chloride (HCl), Hydrogen Cyanide (HCN), Hydrogen Fluoride (HF), Hydrogen Peroxide (H2O2), Hydrogen Selenide (H2Se), Hydrogen Sulfide (H2S), Iodine (I2), Nitric Oxide (NO), Nitrogen Dioxide (NO2), Oxygen (O2), Ozone (O3), Phosgene (COCl2), Phosphine (PH3), Silane (SiH4), Sulfur Dioxide (SO2)
4-20 mA Output Yes
Field Replaceable Sensor No
Auto Test Generator None
Voltage Output None
Power Requirements 12-30 VDC
Accuracy Generally +/-5% of value, but limited by available calibration gas accuracy
Operational Temperature Range -30 to +55C
Operating Pressure 7-30 PSIA
Warranty 1 Year
Audible Alarm No
Calibration 6 Months
Sensor Life 1 Year
Range Gas Dependent
Unit Features

-4-20 mA Output

-Optional Display

-Can be Loop Powered

Sensor Range

Gas Dependent

Integrated Relays No
Sensor Range

Gas Dependent

Write Your Own Review
You're reviewing:B12 Ozone Detector
We found other products you might like!
Loading...